Draft Report on Cowboys Facility Collapse Released for Comment
A fabric-covered, steel frame practice facility owned by the National Football League’s Dallas Cowboys collapsed under wind loads significantly less than those required under applicable design standards, according to a report released on October 6 for public comment by the Commerce Department's National Institute of Standards and Technology (NIST).
Located in Irving, Texas, the facility collapsed on May 2, 2009, during a severe thunderstorm. Twelve people were injured, one seriously.
Based on the national standards for determining loads and for designing structural steel buildings, NIST researchers studying the Cowboys facility found that the May 2 wind load demands on the building’s framework—a series of identical, rib-like steel frames supporting a tensioned fabric covering—were greater than the capacity of the frame to resist those loads.
Assumptions and approaches used in the design of the Cowboys facility led to the differences between the values originally calculated for the wind load demand and structural frame capacity compared to those derived by the NIST researchers. For instance, the NIST researchers included internal wind pressure due to the presence of vents and multiple doors in their wind load calculations because they classified the building as "partially enclosed" rather than "fully enclosed" as stated in the design documents. The NIST researchers also determined that the building’s fabric could not be relied upon to provide lateral bracing (additional perpendicular support) to the frames in contrast to what was stated in the design documents and that the expected wind resistance of the structure did not account for bending effects in some members of the frame.
"Our investigation found that the facility collapsed under a wind load that a building of this type would be expected to withstand," said study leader John Gross. "As a result of our findings, NIST is recommending that fabric-covered steel frame structures be evaluated to ensure the adequate performance of the structural framing system under design wind loads."
The NIST report recommends that such evaluations determine whether or not: (1) the fabric covering provides lateral bracing for structural frames considering its potential for tearing; (2) the building should be considered partially enclosed or fully enclosed based on the openings that may be present around the building’s perimeter; and (3) the failure of one or a few frame members may propagate, leading to a partial or total collapse of the structure.
Shortly after the Cowboys facility’s collapse, NIST sent a reconnaissance team of three structural engineers to assess the failed structure and wind damage in the surrounding area, and collect relevant data such as plans, specifications and design calculations. Using the data acquired during the reconnaissance, the NIST study team developed a computer model of a typical structural frame used in the practice facility and then studied the frame’s ability to resist forces under two wind conditions: the wind loads based on the design standard wind speed of 90 miles per hour and the actual wind loads based on